300 mm Cable Tray Rise at 45° · 400 × 100 mm

Worked 300 mm rise at 45°: 424.26 mm slope, 300 mm horizontal reach and 82.84 mm V-notch for a 400 × 100 mm tray. Includes editable 3D.

The available horizontal run is 900 mm; it includes the lead-in and slope projection, and excludes the final tail.

Calculated answer at a glance

A 300 mm rise at 45° requires an ideal sloped base length of 424.26 mm. It occupies 300 mm horizontally, leaving a 600 mm lead-in inside the stated 900 mm run.

Sloped base length424.26 mm
Horizontal reach300 mm
Lead-in to A600 mm
Original-stock station B1,024.26 mm
Full V opening at A82.84 mm
Opening-side final gap at B76.54 mm

Plan your rise

Edit dimensions ↑
H = 300 mm · θ = 45°

Drag to rotate · pinch or scroll to zoom

Form: close A and open B to level the tail. Toggle the purple connection cover to inspect the opening.

Cutting layout · continuous-base method

Side-wall layout, repeated on both sides. A is the closing bend; B is the opening bend. Stations are measured along the straight base from its starting end.

A · Remove VB · Slit sides2d = 82.84 mmA = 600.00 mm · B = 1024.26 mm · A→B = 424.26 mm

Notch height and small openings are enlarged for readability. Use the labelled dimensions; do not measure from the screen.

● Keep base connected

━ Cut side walls┄ Base fold axis■ Removed material■ Connection cover

At A, remove the V from both walls and fold upward until its edges meet. At B, slit both walls to the base, then counter-fold to make the tail horizontal. The walls open at B: provide a compatible connection detail; purple shows the gap-cover region, not a specified fastener or plate design.

Ideal thin-sheet geometry: excludes kerf, bend radius, rolled lips, material allowance and connection specifications. This method keeps the base joined at both axes; do not cut across it.

Reproduce the calculation

S = 300 / sin(45°) = 424.26 mm. Q = 300 / tan(45°) = 300 mm. A = 900 − Q = 600 mm. B = A + S = 1,024.26 mm.

2d = 2 × 100 × tan(45° / 2) = 82.84 mm.

Read the two different distances

B = 1,024.26 mm is measured along the original straight base. The 900 mm run is a horizontal projection of the formed tray. They are different measurements, so do not put the projected run onto the straight blank as station B. The model tail is 200 mm and is excluded from that run.

Section size and fabrication limits

The 100 mm wall height controls the notch opening; the 400 mm base width sets the cross-section. These ideal geometric lengths apply independently of material choice, but they do not establish that galvanized steel, stainless steel or FRP can use the same cutting and folding process. Bend radius, kerf, rolled lips, material allowance and connection hardware require a suitable fabrication method.

Compare nearby cases

General vertical offset calculator ↗
All worked examples ↗