Cable Tray Below a Beam with Side-Wall Clearance

Calculate a four-fold cable tray route below a beam. Include beam underside, clearance and tray side height, then inspect stock stations and the editable 3D route.

Inspect the 3D example ↗

Reference the underside to the incoming base

This route descends below a hanging beam, passes beneath it and rises back to the incoming tray level. Measure the beam underside as a positive downward distance from the incoming base plane. Measure beam length along the route. Enter the clearance above the highest part of the tray side wall.

The example places the beam underside 150 mm below the incoming base. Clearance is 50 mm and tray side height is 50 mm. The lower base must drop by 150 + 50 + 50 = 250 mm. At that level the wall top is 200 mm below the incoming base, giving the requested 50 mm gap below the beam.

Use a 200 mm wide tray, 400 mm beam length, 45° slopes and 350 mm lead and tail. Side height is part of this vertical clearance calculation. Locate both wall tops in the formed side view before transferring the dimensions to material.

Calculate both slopes and the lower middle section

For base-level drop R and slope angle θ, each sloped base length is S = R / sin θ and its horizontal projection is Q = R / tan θ. With R = 250 mm and θ = 45°, S = 353.55 mm and Q = 250 mm. Both diagonal base sections have the same length.

The lower middle axis spacing is P = O + 2[c + h tan(θ/2)], using beam length O, clearance c and wall height h. Here P = 400 + 2[50 + 50 tan 22.5°] = 541.42 mm. The lead, two slopes, middle and tail add to 1948.53 mm of straight stock.

Worked example dimensions

Calculated from the example inputs above
MeasurementValue
Underside below the incoming base150 mm
Clearance above the tray wall50 mm
Tray side height50 mm
Required base-level drop250 mm
Each sloped base length353.55 mm
Lower middle fold-axis spacing541.42 mm
Closing V width / formed opening gap41.42 mm / 38.27 mm
Total straight stock1,948.53 mm
Open these inputs in the calculator ↗

Inspect the opening and closing joint pairs

The stock stations are 350, 703.55, 1244.97 and 1598.53 mm, with turn sequence −45°, +45°, +45°, −45°. Folds 1 and 4 open side-wall slits during forming. Folds 2 and 3 close side-wall V cuts. Preserve the base connections shown at all four joints.

At the closing pair the full V width is 2h tan(θ/2) = 41.42 mm. At the opening pair the fully formed wall-top gap is 2h sin(θ/2) = 38.27 mm. Follow Original, Mark, Cut and Form to read each measurement at its corresponding stage, then check the complete wall profile below the beam.

L1 · 350 mmL2 · 353.55 mmL3 · 541.42 mmL4 · 353.55 mmL5 · 350 mmStraight stock: 1,948.53 mm · W 200 mm · H 50 mm
Calculated geometry for the worked example. The interactive model below shows the intermediate stages.

Review the fabrication detail

The route uses ideal sharp folds. Check the actual profile, lips, material allowances, joint covers and the space required by the cable path against the product instructions and site dimensions.

Continue with a related layout

Cable Tray Bridge Over an Obstacle — Worked Layout ↗

Centered Cable Tray Reducer — Panel Lengths and Assembly ↗

Cable Tray Column Bypass with Width and Clearance ↗

One-Sided Cable Tray Reducer with One Edge Aligned ↗

Cable Tray Through a Wall Opening with Clearance ↗

Horizontal Cable Tray S Offset and Stock-Axis Spacing ↗

Cable Tray U Return with Four 45 Degree Folds ↗

Cable Tray 90 Degree Turn with Three 30 Degree Folds ↗

Cable Tray 90 Degree Turn with Four 22.5 Degree Folds ↗

Cable Tray Expander from 200 to 400 mm ↗

Equal-Slope Rectangular Funnel Panel Layout ↗

Try the layout with your dimensions

The model starts with the worked example. Edit the inputs, apply the calculation, then inspect the marking, cutting and forming stages.

Geometry parameters

Edit dimensions ↑
L1 · 350 mmL2 · 353.55 mmL3 · 541.42 mmL4 · 353.55 mmL5 · 350 mmStraight stock: 1,948.53 mm · W 200 mm · H 50 mm

Drag to rotate · pinch or scroll to zoom

Fold about every retained axis. Purple covers identify opening regions; they do not specify hardware.

Straight-stock marking and joint schedule

L1 · 350 mmL2 · 353.55 mmL3 · 541.42 mmL4 · 353.55 mmL5 · 350 mmStraight stock: 1,948.53 mm · W 200 mm · H 50 mm
FoldStock station (mm)θClosing V full width (mm)Opening slit · formed gap (mm)
1350-45.00°—38.27
2703.5545.00°41.42—
31,244.9745.00°41.42—
41,598.53-45.00°—38.27

Ideal zero-radius geometry. Cut envelopes, retained folds and opening covers are shown explicitly; kerf, rolled lips, thickness allowances, cable clearance, springback and connection hardware are not specified.